What is a reverberation time test?

A reverberation time test measures how quickly sound decays in a room, reported in seconds per frequency band. For ordinary rooms the procedure is specified in ISO 3382-2, and BB93 compares the result, as a mid-frequency average, with its limit for the room type in a finished, furnished and unoccupied room.[1][2]

Key points

  • ISO 3382-2 specifies the measurement procedure, the apparatus, the number of measurement positions and the method for evaluating the data and presenting the test report.[1]
  • BB93's reverberation time limits apply to rooms that are finished and furnished for normal use but unoccupied.[2]
  • The result is compared as Tmf, the average of the 500 Hz, 1 kHz and 2 kHz octave bands, or of the one-third octave bands from 400 Hz to 2.5 kHz.[2]
  • The design guide recommends at least one reverberation time test in each type of room when establishing the baseline of an existing building.[3]

How it works

The standard describes what a test has to include. ISO 3382-2:2008 sets out the measurement procedure, the equipment, how many measurement positions are needed, how the data are evaluated and how the test report is presented.[1] Its results can be used to correct other acoustic measurements and for comparison with requirements for reverberation time in rooms.[1] The standard was last reviewed and confirmed in 2022.[1] The full method is in the paywalled standard; this page reports only what the publisher's catalogue entry and the cited school guidance state.

BB93 adds the school conditions. Its limits are for rooms that are finished and furnished for normal use but unoccupied, and for unfurnished halls it accepts either design to the Institute of Acoustics guide or measurement following the Association of Noise Consultants testing guide.[2]

The numbers

BB93 maximum Tmf for the room types, with the measured value compared against the new build or refurbishment column as appropriate:[2]

  • Nursery or primary classroom, class base, small group room or SEN calming room: 0.6 s new build, 0.8 s refurbishment.[2]
  • Secondary classroom, study room, science laboratory: 0.8 s new build, 1.0 s refurbishment.[2]
  • Open plan teaching area: 0.5 s new build and refurbishment.[2]
  • Teaching space intended specifically for students with special hearing and communication needs: 0.4 s averaged from 125 Hz to 4 kHz and no octave band above 0.6 s, new build; 0.4 s for refurbishment.[2]

In schools and SEN settings

BB93 says pre-completion testing and reporting should be carried out by a specialist acoustic consultant in accordance with the Association of Noise Consultants Good Practice Guide to acoustic testing of schools.[2] For rooms intended specifically for pupils with special hearing and communication needs the test result is averaged over a wider band, 125 Hz to 4 kHz octave bands, or 100 Hz to 5 kHz one-third octave bands, so the low-frequency decay is part of the result.[2] The design guide also says the person testing should note subjective impressions such as whether sound seemed boomy or fixtures rattled, because exposed services can cause an anomalous increase in measured reverberation time.[3] It adds that if new suspended ceilings are proposed it may not be necessary to measure reverberation times, unless the results are needed to inform the ceiling specification.[3]

Worked example

These figures are illustrative. A test in a new build primary classroom gives 0.74 s at 500 Hz, 0.66 s at 1 kHz and 0.58 s at 2 kHz.[2] Tmf is (0.74 + 0.66 + 0.58) / 3 = 0.66 s.[2] That is above the 0.6 s new build limit and below the 0.8 s refurbishment limit, so the room fails as new build.[2] The band values show most of the excess is at 500 Hz.[2]

What people get wrong

  • Testing a room under construction. BB93's limits describe a finished, furnished, unoccupied room.[2]
  • Comparing with the wrong column. BB93 says the refurbishment figures should not normally be used for new build.[2]
  • Reading a single band. The limit is on the average of the mid-frequency bands, except for special hearing and communication needs rooms where an upper band limit also applies.[2]

How it is measured

The method is the ISO 3382-2 procedure for ordinary rooms; ISO 3382-1 covers performance spaces and derives room acoustic parameters from impulse responses.[1][4] The design guide notes that where a sports hall is designed by calculation and installed as designed, commissioning measurement of reverberation time would not be required.[3]

FAQ

Which standard governs the test?

ISO 3382-2 for ordinary rooms.[1]

What condition must the room be in?

BB93's values are for finished rooms, furnished for normal use, but unoccupied.[2]

Who should carry out school testing?

BB93 says a specialist acoustic consultant, following the Association of Noise Consultants guide.[2]

What result does a classroom need?

At most 0.6 s Tmf for new build primary and 0.8 s for secondary classrooms.[2]

WorkSpace Acoustics surveys and installs acoustic treatment; contact the team to talk about a room.

Sources

  1. ISO 3382-2:2008 Acoustics: Measurement of room acoustic parameters, Part 2: Reverberation time in ordinary rooms. International Organization for Standardization, June 2008, confirmed 2022. Accessed November 2026.
  2. Acoustic design of schools: performance standards (Building Bulletin 93). Department for Education, February 2015. Accessed November 2026.
  3. Acoustics of Schools: a design guide. Institute of Acoustics and Association of Noise Consultants, November 2015. Accessed November 2026.
  4. ISO 3382-1:2009 Acoustics: Measurement of room acoustic parameters, Part 1: Performance spaces. International Organization for Standardization, June 2009. Accessed November 2026.
Expert acoustic consultancy and installation for schools, businesses and restaurants across the UK. Specialists in SEN environments.
A specialist division of: Presentation Spaces Group

COMPANY

About
Why Acoustics
Contact Us
Privacy Policy
Glossary
Acoustics statistics

SECTORS

Schools
Businesses
Restaurants

SERVICES

Acoustic Surveys
Acoustic Design
Installation
© 2026 WorkSpace Acoustics Ltd. All rights reserved.
Product images courtesy of Presentation Spaces Group (used with permission)