What is retrofit acoustic treatment?
Retrofit acoustic treatment is acoustic improvement of a room in an existing building, such as adding absorption to a ceiling or walls. BB93 gives separate refurbishment values, for example a reverberation time of 0.8 s for a primary classroom against 0.6 s for new build, and recommends aiming for new build values where possible.[1]
Key points
- BB93 says refurbishment values should not normally be used for new build, and are the minimum acceptable standard for Building Regulations purposes in refurbishments.[1]
- Where new elements such as ceilings are installed in a refurbishment, the target should where possible be at least the new build standard.[1]
- The School Premises Regulations and Independent School Standards apply to refurbishment work whether or not there is a material change of use.[1]
- The design guide suggests testing the existing building first to establish its performance.[2]
How it works
BB93 explains the legal setting. Building Regulations do not apply to all alteration and refurbishment work, but it is desirable that such work considers acoustics, and Regulation 4 requires that building work does not make an existing requirement or contravention worse.[1] Where there is a material change of use, the work should ensure compliance with Requirement E4, using BB93's refurbishment criteria.[1]
BB93 says refurbished elements should meet the guidance as far as reasonably practicable.[1] Sound insulation between rooms depends on construction and flanking paths, and pre-existing flanking elements can limit what is achievable.[2]
The numbers
BB93 values for refurbishment against new build:[1]
- Primary classroom Tmf: 0.8 s refurbishment, 0.6 s new build.[1]
- Secondary classroom Tmf: 1.0 s refurbishment, 0.8 s new build.[1]
- Classroom indoor ambient noise: 40 dB LAeq,30mins refurbishment, 35 dB new build.[1]
- Classroom to classroom DnT,w: 40 dB refurbishment, 45 dB new build.[1]
- Teaching space for students with special hearing and communication needs: Tmf 0.4 s for refurbishment, and 0.4 s averaged from 125 Hz to 4 kHz plus 0.6 s in every octave band for new build.[1]
In schools and SEN settings
BB93 says there is considerable educational benefit in achieving the new build reverberation times in refurbished teaching spaces.[1] For rooms intended specifically for pupils with special hearing and communication needs the BB93 reverberation figure is 0.4 s for refurbishment as well, with an indoor ambient noise limit of 35 dB against 30 dB for new build.[1] The design guide warns that where flanking elements are pre-existing, for example new partitions connected to the back of existing mullions, sound insulation will invariably be poor and it may not be possible to meet even the reduced refurbishment standards, so the client should be told early.[2] Where listings or planning restrictions apply, scope for improvement may be limited.[2]
Worked example
These figures are illustrative. An existing primary classroom measures a Tmf of 0.95 s.[1] Against the refurbishment limit of 0.8 s it is 0.15 s over; against the new build limit of 0.6 s it is 0.35 s over.[1] If a new suspended ceiling is installed as part of the work, BB93 says the aim should be at least the new build standard, 0.6 s.[1]
What people get wrong
- Treating refurbishment figures as the target. They are the minimum acceptable, and BB93 says to aim higher where new elements go in.[1]
- Skipping the baseline. Testing first shows where the room is, and it may already meet its targets.[2]
- Expecting treatment to fix insulation. Sound insulation depends on construction and flanking paths.[2]
How it is measured
The baseline and outcome are measured with the methods in the acoustic survey and testing pages: reverberation time following ISO 3382-2, airborne insulation following ISO 16283-1.[3][4] The design guide adds that if new suspended ceilings are proposed, measuring reverberation time may be unnecessary unless needed to inform the ceiling specification.[2]
FAQ
Does BB93 apply to refurbishment?
Yes; the School Premises Regulations and Independent School Standards apply, using the refurbishment values.[1]
Are refurbishment limits lower than new build?
They are more relaxed: for example 0.8 s against 0.6 s for a primary classroom.[1]
Should I test before treating a room?
The design guide suggests testing existing performance as a minimum basis.[2]
Can every old room reach the standard?
No; flanking and listed-building restrictions can limit what is achievable.[2]
WorkSpace Acoustics surveys and installs acoustic treatment; contact the team to talk about a room.
Sources
- Acoustic design of schools: performance standards (Building Bulletin 93). Department for Education, February 2015. Accessed November 2026.
- Acoustics of Schools: a design guide. Institute of Acoustics and Association of Noise Consultants, November 2015. Accessed November 2026.
- ISO 3382-2:2008 Acoustics: Measurement of room acoustic parameters, Part 2: Reverberation time in ordinary rooms. International Organization for Standardization, June 2008, confirmed 2022. Accessed November 2026.
- ISO 16283-1:2014 Acoustics: Field measurement of sound insulation in buildings and of building elements, Part 1: Airborne sound insulation. International Organization for Standardization, February 2014. Accessed November 2026.