What are the acoustic requirements for a meeting room?

Meeting room acoustics are the reverberation, background noise and sound insulation conditions that let a small group hear each other and keep a discussion private. The only freely published UK figures are in BB93, which gives school meeting rooms 40 dB LAeq,30min ambient noise and 0.8 s reverberation for new build.[1]

Key points

  • BB93 groups meeting rooms, interviewing and counselling rooms and video conference rooms in one row of its tables.[1]
  • The BB93 reverberation limit for this row is 0.8 s for both new build and refurbishment.[1]
  • BS 8233:2014 is the British Standard for noise control in and around buildings, and its page says it covers room acoustics for non-critical situations. It is not free to read, so its values are not reproduced here.[2]
  • The figures below are school figures. They are a reference point for a meeting room elsewhere, not a standard for it.[1]

How it works

In a meeting room, speech needs to be clear for people at a table and quiet enough outside the room that a conversation stays private. Reverberation blurs speech and background noise masks it, which is the same mechanism the Institute of Acoustics describes for classrooms: a long reverberation time makes syllables overlap and lowers intelligibility.[3]

BB93 sets the room's limits using a classification of activity noise and noise tolerance. A meeting room is classed as low activity noise and medium noise tolerance, so it can be placed next to other rooms using the same table of insulation values as classrooms.[1]

The numbers

BB93 gives these values for finished, furnished and unoccupied rooms.[1]

  • Meeting room, interviewing or counselling room, video conference room, indoor ambient noise: 40 dB LAeq,30min new build, 45 dB refurbishment.[1]
  • The same rooms, reverberation Tmf: 0.8 s or less for both new build and refurbishment.[1]
  • Impact sound pressure level as a receiving room: no more than 60 dB L'nT,w new build, 65 dB refurbishment.[1]
  • Airborne sound insulation into a meeting room from a source with average activity noise: at least 45 dB DnT,w new build, 40 dB refurbishment.[1]

In schools and SEN settings

BB93 includes meeting rooms and interviewing or counselling rooms among school room types.[1] The design guide says induction loop or infra red hearing aid systems are mainly for visitors to the school, since pupils normally have their own assistive listening equipment, and that such systems should be considered in meeting rooms and at reception area desks.[3] It recommends seeking advice to make sure all public spaces in a school meet the needs of people with special hearing requirements.[3]

Worked example

These figures are illustrative, using the BB93 school meeting room value for a room of any kind. A meeting room of 5 m by 4 m with a 2.7 m ceiling has a volume of 54 m³.[3] The Sabine relation quoted in the design guide gives total absorption for 0.8 s of 0.161 × 54 ÷ 0.8 = 10.9 m².[3]

What people get wrong

  • Assuming a school figure is a corporate standard. BB93 is for schools, and BS 8233 or a project specification governs other buildings.[1][2]
  • Treating reverberation alone as privacy. Privacy depends on insulation and background noise as well as the room's own acoustics, as BB93's separate insulation tables show.[1]
  • Using refurbishment limits as the new build target. BB93 says refurbishment values are the minimum acceptable standard for alternative performance standards in new buildings, not the target, and gives 45 dB rather than 40 dB for a refurbished meeting room.[1]

How it is checked

BB93 says pre-completion testing and reporting should be done by a specialist acoustic consultant, and the same approach suits any office: measure ambient noise, reverberation time and sound insulation, and compare them with the project brief.[1]

FAQ

What is a good reverberation time for a meeting room?

BB93 gives 0.8 s or less for a school meeting room, new build or refurbishment.[1]

How quiet should a meeting room be?

BB93 sets 40 dB LAeq,30min for new build and 45 dB for refurbishment in a school meeting room.[1]

Which standard applies to a commercial meeting room?

BS 8233:2014 covers noise control in buildings and is not free to read, so check it or the project specification rather than a school figure.[2]

WorkSpace Acoustics surveys and installs acoustic treatment; contact the team to discuss a room.

Sources

  1. Acoustic design of schools: performance standards (Building Bulletin 93). Department for Education, February 2015. Accessed November 2026.
  2. BS 8233:2014 Guidance on sound insulation and noise reduction for buildings. British Standards Institution, 28 February 2014. Accessed November 2026.
  3. Acoustics of Schools: a design guide. Institute of Acoustics and Association of Noise Consultants, November 2015. Accessed November 2026.
Expert acoustic consultancy and installation for schools, businesses and restaurants across the UK. Specialists in SEN environments.
A specialist division of: Presentation Spaces Group

COMPANY

About
Why Acoustics
Contact Us
Privacy Policy
Glossary
Acoustics statistics

SECTORS

Schools
Businesses
Restaurants

SERVICES

Acoustic Surveys
Acoustic Design
Installation
© 2026 WorkSpace Acoustics Ltd. All rights reserved.
Product images courtesy of Presentation Spaces Group (used with permission)