What is a Euroclass fire rating?
A Euroclass is a reaction-to-fire classification for construction products, from A1 (best) to F (worst), assigned under BS EN 13501-1. Classes A2 to E add a smoke rating, s1 to s3, and a flaming droplets rating, d0 to d2. For example, B-s1,d0 is class B with the lowest smoke and droplet ratings.[1][2]
Key points
- Products other than floorings are classified A1, A2, B, C, D, E or F, with A1 the highest performance and F the lowest.[1]
- Class F is assigned when a product fails to attain class E, and untested products cannot be classified.[1]
- The smoke classes are s1, s2 and s3 (s1 lowest), and the flaming droplet classes are d0, d1 and d2 (d0 lowest). A classification of s3, d2 means no limit is set for either.[1]
- A class is valid only within the product's direct field of application, which includes the substrate it is fixed to.[1]
How it works
The Euroclass system comes from BS EN 13501-1, which gives the classification procedure from reaction to fire test data.[2] Reaction to fire is how a product contributes, by its own decomposition, to a fire under specified conditions.[1] Floorings are classified separately from other construction products under the standard.[1][2]
Approved Document B explains that the classification achieved in testing is only valid when the product is used within its direct field of application, so a product tested fixed to a plasterboard substrate is not automatically classified for another substrate.[1] Check the classification report for the exact end-use conditions.
Euroclass B-s1,d0
The label "B-s1,d0" reads as three parts: B is the main class, s1 is the lowest smoke production rating, and d0 is the lowest rating for flaming droplets or particles.[1] This page states no product's class. Approved Document B says untested products cannot be classified, so a product's classification report is the evidence for its class.[1] Whether B-s1,d0 is needed for a room is a question for Approved Document B and the building control body; Table 6.1 below shows the minimum for ordinary rooms is lower.[1]
The numbers
Approved Document B Volume 2 Table 6.1 sets the minimum classification for the surface linings of walls and ceilings.[1]
- Small rooms up to 30 m2 in non-residential accommodation: D-s3, d2.[1]
- Other rooms, including garages: C-s3, d2.[1]
- Other circulation spaces: B-s3, d2.[1]
- Parts of walls in a room may be lower, but no worse than D-s3, d2, with a total area under half the floor area up to a maximum of 60 m2 in non-residential accommodation.[1]
In schools and SEN settings
BB93 says free-hanging acoustic baffles are not part of the ceiling but should have the appropriate spread of flame classification, and that certificates of conformity are part of the Building Regulations approval process.[3] The Euroclass table above applies to wall and ceiling linings in non-residential accommodation, which covers teaching rooms.[1] BB93 refers designers to Building Bulletin 100 and Approved Document B for further guidance.[3]
The old national classification route has gone from the guidance. The 2025 amendments to Approved Document B removed the national classes for reaction to fire, and BSI says BS 476-7 is superseded by BS EN 13823.[1][4]
Worked example
An illustrative corridor lining is tested and classified C-s2, d0. Table 6.1 requires B-s3, d2 for circulation spaces, so class C does not meet it, since B ranks above C.[1] The same lining would meet the C-s3, d2 requirement for an ordinary room, because s2 is better than s3 and d0 is better than d2.[1] This is invented, to show how to read the table.
What people get wrong
- Reading the letter alone. The class needs the s and d sub-classes: B alone is not B-s1,d0.[1]
- Assuming a tested class travels to any substrate. It is valid only in the direct field of application.[1]
- Using old BS 476 numbers. BSI says the reaction to fire parts were removed from Approved Document B on 2 March 2025.[4]
FAQ
What is the best Euroclass?
A1 is the highest performance class and F the lowest.[1]
What does s1, d0 mean?
s1 is the lowest smoke production rating and d0 is the lowest rating for flaming droplets or particles.[1]
Which Euroclass do school classrooms need?
Approved Document B sets C-s3, d2 for other non-residential rooms and D-s3, d2 for small ones up to 30 m2.[1] Check with building control for a project.
WorkSpace Acoustics surveys and installs acoustic treatment for schools; see the products or contact the team.
Sources
- Fire safety: Approved Document B, Volume 2: Buildings other than dwellings. Ministry of Housing, Communities and Local Government, 2019 edition incorporating amendments to 2026. Accessed November 2026.
- BS EN 13501-1:2018 Fire classification of construction products and building elements: Classification using data from reaction to fire tests. BSI, 31 January 2019. Accessed November 2026.
- Acoustic design of schools: performance standards (Building Bulletin 93). Department for Education, February 2015. Accessed November 2026.
- The changing status of the BS 476 standard series: A summary. BSI, 19 February 2025. Accessed November 2026.