What is BB93 pre-completion testing?
BB93 pre-completion testing, which BB93 calls acoustic commissioning, is the measurement of ambient noise, sound insulation and reverberation time in a finished school by a specialist acoustic consultant, following the Association of Noise Consultants testing guide. Building Regulations do not require it, but BB93 strongly recommends it for contractual purposes.[1]
Key points
- BB93 section 2.3 says pre-completion testing and reporting should be carried out by a specialist acoustic consultant using the Association of Noise Consultants "Good Practice Guide: Acoustic Testing of Schools".[1]
- There is no requirement in the Building Regulations for acoustic commissioning of schools, although BB93 strongly recommends it for contractual purposes.[1]
- BB93 does not describe a certificate. Before construction, intent to comply is shown to the building control body with plans, construction details, material specifications and calculations.[1]
- BB93 limits apply to rooms that are finished and furnished for normal use but unoccupied, so testing happens at the end of the build.[1]
How it works
Before construction, the design team submits plans, details, specifications and calculations to the building control body for each area covered by Requirement E4 of the Building Regulations.[1] Testing is the later check that the finished rooms match the design. The client decides whether to require it, and BB93 recommends writing it into the building contract.[1]
The tests compare measured results with the limits in BB93. These cover the upper limit for indoor ambient noise in LAeq,30min, airborne and impact sound insulation, and mid-frequency reverberation time.[1] The Institute of Acoustics and Association of Noise Consultants design guide notes that a standardised level difference, DnT,w, is used for design, while a different single-number rating, Dw, is allowed for commissioning tests but not for design.[2]
The numbers
BB93 section 2.3 refers to the Association of Noise Consultants guide for the procedures and gives no sampling rate itself; this page does not reproduce that guide.[1] Two published figures show how sampling can work.
- For a refurbishment, the design guide suggests as a minimum two airborne sound insulation tests across each type of partition, two across each type of floor, two impact tests across each type of floor, and one reverberation time test in each type of room, to record existing performance.[2]
- Scotland's optional Gold sustainability level for new schools asks for testing in at least one room in every four of each type of classroom, with an additional room tested after any failure.[3]
In schools and SEN settings
BB93 says rooms intended specifically for pupils with special hearing or communication needs have tighter limits, and that the criteria for these spaces should be signed off by the school client body in the same way as alternative performance standards.[1] The design guide says its sound insulation standards for these rooms are more stringent and apply across 125 Hz to 4 kHz.[2] A test plan for such a room therefore needs to cover that wider frequency range and the agreed criteria, not only the standard classroom table.
Worked example
An illustrative new school has 12 identical classrooms and is built to the Scottish optional Gold level. One room in every four of that type must be tested, so three rooms are tested.[3] If one fails, one more room of that type is identified and tested, and if that also fails all remaining rooms of the type must be tested and remedial work carried out.[3]
What people get wrong
- Treating testing as a legal step in England. BB93 states there is no requirement in the Building Regulations for acoustic commissioning.[1]
- Expecting a certificate. BB93 describes a test report by a specialist acoustic consultant and submitted design evidence, not a certificate.[1]
- Testing furnished-room limits in an empty shell. BB93 limits assume rooms are finished and furnished for normal use.[1]
How it is measured
BB93's reference list names these measurement standards: ISO 16283-1 for field airborne sound insulation, ISO 140-7 for impact sound, ISO 16032 for service equipment noise and ISO 717-1 and 717-2 for the ratings.[1] Reverberation time in ordinary rooms is measured to ISO 3382 part 2.[2] The design guide also says testers should note whether sound seemed boomy, fixtures rattled or flanking paths were present, because those observations inform the design.[2] For sports halls and similar unfurnished spaces, BB93 accepts either design to the design guide or measured Tmf.[1] The design guide adds that when the sports hall design method is followed and the materials are installed as calculated, commissioning measurements of reverberation time would not be required.[2]
FAQ
Who pays for and arranges pre-completion testing in a school?
BB93 recommends the client requires it in the building contract; it does not name who pays.[1]
Is a failed test a Building Regulations failure?
BB93 states there is no requirement in the Building Regulations for acoustic commissioning, so a test result is a contractual matter first. Check with the building control body or a legal adviser for a particular project.[1]
Is there a BB93 product certificate?
No. BB93 sets performance limits for rooms and describes no product certificate.[1]
WorkSpace Acoustics surveys and installs acoustic treatment for schools; contact the team to discuss a room.
Sources
- Acoustic design of schools: performance standards (Building Bulletin 93). Department for Education, February 2015. Accessed November 2026.
- Acoustics of Schools: a design guide. Institute of Acoustics and Association of Noise Consultants, November 2015. Accessed November 2026.
- Building standards technical handbook: non-domestic, Section 7 Sustainability. Scottish Government, April 2026. Accessed November 2026.